Motor Cable Size Chart: Cross-Section and Length by Motor Power

Permitted cable lengths at 3% voltage drop by motor power, voltage and starting method, with direct-on-line and star-delta charts and a selector tool.

ORFA Technical TeamUpdated: Oct 30, 20268 min read
Motor cable size chart – cable cross-section by motor power

A motor cable size chart is used to select the cross-section of the cable feeding an electric motor according to motor power, supply voltage, starting method and cable length. On long runs the cable resistance causes a voltage drop; too low a voltage at the motor terminals leads to difficult starting, overcurrent and overheating.

The charts below give the maximum permitted cable length in metres for each cross-section, based on a 3% voltage drop and an ambient temperature of 25 °C. Direct-on-line values for 220 V (single-phase) and 380 V (three-phase), and star-delta values for 380 V, are given in separate tables.

How to Use the Chart

  1. Determine the motor power (kW or HP) and starting method.
  2. Find the motor power row in the relevant table.
  3. In that row, choose the cross-section of the first column whose value is equal to or greater than your cable length.

Example: A 15 kW (20 HP) motor, direct-on-line at 380 V, is fed by a 100 m cable. In the 15 kW row the maximum length is 80 m for 6 mm² and 130 m for 10 mm². For 100 m, a 3 × 10 mm² cable is selected.

Tip: With star-delta starting two separate three-core cables run to the motor, and each carries about 1/√3 of the line current. The permitted length for the same cross-section is therefore about 1.5–1.7 times that for direct-on-line starting.

Cable Size Selector

The tool selects the motor rating equal to or next above the power entered and finds the smallest cross-section whose tabulated length covers your cable run. Current-carrying capacity and protective devices must be checked separately.

Cable Chart 1 – Direct-on-Line, 220 V (Single-Phase)

HPkWCable cross-section 3 × … mm² – maximum length (m)
1.52.54610162535507095120150
0.50.3780130–––––––––––
0.750.555590140––––––––––
10.754080105160–––––––––
1.51.1305075115190––––––––
21.520356090145235–––––––
32.2–305070120185–––––––

Cable Chart 2 – Direct-on-Line, 380 V (Three-Phase)

HPkWCable cross-section 3 × … mm² – maximum length (m)
1.52.54610162535507095120150
10.75230––––––––––––
1.51.1180235–––––––––––
21.5135225360––––––––––
32.2–190300460–––––––––
43–150240360–––––––––
5.54–110170260450––––––––
7.55.5–80150190340540–––––––
107.5–60100150250410–––––––
12.59.2–5080120205330510––––––
1511––60100170280440––––––
17.513–––90150245385––––––
2015–––80130210330460660––––
2518.5––––100170260370530––––
3022––––90140220310440––––
3526–––––120190270380540–––
4030–––––100170230330460–––
5037––––––130190270380520––
6045––––––110160230320440550–
7052–––––––140200280385480–
7555–––––––120170240330410530
8059–––––––115160230310390500
9066–––––––110150220290370470
10075–––––––96140190270350425
11081––––––––125175245300380
12592––––––––110160220275340
150110–––––––––130180220290
180132––––––––––150190240
200150––––––––––130170190
225165––––––––––125150190
250185––––––––––––170
275200––––––––––––160

Cable Chart 3 – Star-Delta, 380 V

HPkWCable cross-section 3 × … mm² – maximum length (m)
1.52.54610162535507095120150
43140230370––––––––––
5.54100170270400–––––––––
7.55.570120200300500––––––––
107.55790150220380––––––––
12.59.24670120180310490–––––––
15113960100150260400–––––––
17.513–5590130230355–––––––
2015–5080110200310490––––––
2518.5––6090160250400560–––––
3022––5070130210340470–––––
3526––4668110180290410–––––
4030–––60100160250360500––––
5037–––4080130200290410––––
6045––––70110170240350480–––
7052–––––95150210305420–––
7555–––––80130180260360500––
8059––––––120170245340475––
9066––––––110160230320450520–
10075––––––100150200290380440540
11081–––––––135185260340405495
12592–––––––120170230300370450
150110–––––––100140200250300370
180132––––––––120165210260310
200150–––––––––150190230280
225165–––––––––130170200240
250185–––––––––125160190230
275200––––––––––140170200

Values are maximum lengths (m) for copper conductor cables, calculated for a 3% voltage drop at 25 °C. A dash (“–”) means the section is not suitable for that power or no value is given.

Frequently Asked Questions

Is cable size selected on voltage drop alone?

No. Besides voltage drop, the current-carrying capacity (depending on installation method and ambient temperature), short-circuit withstand and coordination with protective devices must also be checked. The chart gives a preliminary selection with respect to length.

What if the ambient temperature is higher?

Conductor resistance rises with temperature, which reduces the permitted length for the same section and lowers current-carrying capacity. In hot environments the next larger section may be needed.

Can the chart be used for submersible pumps?

The chart is for general motor supplies. For submersible pump motors, use the manufacturer’s cable tables and permitted voltage drop.

Conclusion

The correct cable cross-section is essential for safe starting, efficient operation and long motor life. With the charts and selector you can quickly determine the section from motor power and cable length. For electric motors and pump accessories, see our pump accessories and spare parts product group.

Online Store

Buy electric motors online

Browse products on or-fa.com, our export store, see prices in USD and order online.

Buy Online →Request a QuoteAsk on WhatsApp

Technical support

Talk to our team to choose the right product.
+90 224 444 67 32[email protected]

Related Articles

Let’s choose the right product for your project

Buy from our online store or request a project-specific quotation.