Engineering Calculators

Water Pipe Sizing Calculator

Find the required inner diameter and DN size from flow rate and target water velocity; see the velocity and pressure loss per metre in the selected size.

Results are for preliminary selection only; check the manufacturer catalogue or consult the ORFA technical team for final selection.

How is it calculated?

The required inner diameter is D = √(4·Q / (π·V)), rounded up to the next standard steel pipe size. The actual velocity and the pressure loss per metre (Darcy–Weisbach) are shown for the selected size. Keep velocity below 2.5 m/s to avoid noise and erosion.