Storage Sprinklers

Storage sprinklers are large-orifice heads designed to deliver high water flow to fast-growing fires in high-piled and rack storage. Compared with standard sprinklers they produce larger droplets and higher flow so the water penetrates the fire plume and reaches the burning goods.
This group contains two families: large-orifice ELO sprinklers for fire control and ESFR sprinklers developed to suppress the fire at an early stage. Models in the store range have a ¾” connection.
Main Applications
- High-rack logistics warehouses
- Palletised and block storage areas
- Plastic and cardboard packaging stores
- Automated storage systems
- Large production halls
Technical Data
| Families | ELO (large orifice) and ESFR (early suppression, quick response) |
|---|---|
| Connection | ¾” (product range) |
| ELO ratings | 68, 79, 93, 141 °C (product range) |
| ESFR ratings | 74 °C and 96 °C (product range) |
| Mounting | Pendent and upright (product range) |
| K-factor | By model |
| Design | By storage height, storage type and commodity class |
| Approval | UL / FM certificate by model |
Material Options
| Part | ELO sprinkler | ESFR sprinkler |
|---|---|---|
| Purpose | Fire control | Early suppression |
| Response | Standard (by model) | Quick |
| Rating | 68–141 °C | 74 / 96 °C |
| Connection | ¾” | ¾” |
Which material? Storage sprinklers are selected from the fire design standard by ceiling height, storage height and commodity class; ESFR systems may reduce the need for in-rack sprinklers, but that decision depends on the project calculation.
Advantages
High Flow
- Dense water through a large orifice
Penetrates the Plume
- Large droplets reach the burning load
Early Suppression Option
- ESFR puts out the fire while small
Two Mounting Types
- Pendent and upright
Construction and Design Features
- Heavy body with ¾” connection
- Large water outlet orifice
- Wide deflector for high flow
- Bulb or link sized to the temperature rating
Send the warehouse height, storage type and commodity class; we will clarify the choice of ELO or ESFR with your project team.
How to Choose?
- Collect warehouse dataFind ceiling and storage heights and rack type.
- Choose the familyUse ESFR for early suppression and ELO for fire control.
- Set the temperature ratingPick a rating suited to the ceiling temperature.
- Check water demandVerify pump and tank capacity against sprinkler flow.
Complementary Products
Why ORFA?
Types of Storage Sprinklers
Other Fire Sprinklers

Extended Coverage Sprinklers
Extended coverage sprinklers are automatic fire sprinklers that protect a larger area than standard sprinklers.
Details →
Dry Sprinklers
Dry sprinklers are automatic fire sprinklers used in areas at risk of freezing, with no water standing in the body.
Details →
Standard Coverage Sprinklers
Standard coverage sprinklers are automatic fire sprinklers widely used in general areas.
Details →Get a quote for your project